Switch 2
Switch 3
Switch 12
Switch 13
Note : Supervisor system is able to detect if the valve close on torque,
14
and in this case there is no fault indication.
Move switch 2 to position B for loss
of input signal 4-20mA not indicated
as a fault. (Positioner only).
- Loss of input signal 4-20mA is not
a fault. (Only option positioner)
Move switch 3 to position B for
local/remote selector in local or off not
indicated as a fault.
- Local/remote selector in local or off
is not a fault.
Move switch 12 to position B for trip-
ping of torque switch open to be a
fault.
- Tripping of torque switch close is a
fault.
Move switch 13 to position B for
tripping of torque switch close to be
a fault.
- Tripping of torque switch open is
a fault.