Bernard Integral+ Commissioning Instructions page 26

Hide thumbs Also See for Integral+:
Table of Contents

Advertisement

PROBLEM
Torque limiter
indication does not
return to initial reading
once the torque limiter
is no longer actuated.
A fault is indicated
but the actuator
is fully functional.
26
CAUSE
Torque limiter data
storage
The input control signal
is not present. In standard
configuration, the actuator
indicates a fault and
remains in position.
The selector switch
is set to local or off
position. In standard
configuration the actuator
indicates a fault.
CORRECTIVE ACTION
The torque limiter data are stored
electronically.
To clear a torque limiter memory, a reverse
order must be sent.
Send a control signal on the input
Set the selector switch to remote .