8.2
INDICATION RELAY N°1
In standard, relay N°1 indicates limit switch open. Jumper 14 in position LSO (Limit Switch Open).
Jumper 14
Move jumper 14 to position TSO (Torque Switch Open) for relay N°1 to indicate torque switch open.
In standard, relay N°1 is with contact normally open. Jumper 22 in position
Jumper 22
Move jumper 22 to position
close.
- Configuration relay 1: jumpers 14 and 22
8.3
INDICATION RELAY N°2
In standard, relay N°2 indicates limit switch close. Jumper 15 in position LSC (Limit Switch Close).
Jumper 15
Move jumper 15 to position TSC (Torque Switch Close) for relay N°2 to indicate torque switch close.
In standard, relay N°2 is with contact normally open. Jumper 23 in position
Jumper 23
Move jumper 23 to position
closed.
- Configuration relay 2: Jumpers 15 and 23
8.4
INDICATION RELAY N°3
In standard, relay N°3 indicates limit switch open. Jumper 16 in position LSO (Limit Switch Open).
Jumper 16, 17 and 18
NOTE: There is only one jumper for the three jumper holders number 16, 17 and 18
- Move jumper to holder 16 / TSO (Torque Switch Open) for relay N°3 to indicate torque switch
open.
- Move jumper to holder 17 / REMOTE for relay N°3 to indicate local/remote selector
in position remote.
- Move jumper to holder 17 / LOCAL for relay N°3 to indicate local/remote selector
in position local.
- Move jumper to holder 18 / OPENING for relay N°3 to indicate an actuator opening movement.
- Move jumper to holder 18 / RUNNING for relay N°3 to indicate that actuator is running.
In standard, relay N°3 is with contact normally open. Jumper 24 in position
12
for relay N°1 to be with contact normally
for relay N°2 to be with contact normally