6.3

Operation Errors

After the parameters have been set, an operation error will occur if there is an invalid setting or a contradiction between two parameter settings.
It won't be possible to start the power regenerative unit until the parameters have been set correctly. (The minor fault output and fault contact output
will not operate, either.)
When an operation error has occurred, refer to the following table to identify and correct the cause of the errors.
Display
OPE01
kVA Selection
OPE02
Limit
OPE03
Terminal
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
Table 6.3 Operation Error Displays and Incorrect Settings
Meaning
Incorrect Power Regenerative Unit
Capacity Setting
Parameter Setting Range Error
Multi-function Input Selection Error
Incorrect settings
The power regenerative unit capacity setting does not match the Unit. (Contact
your YASKAWA representative.)
The parameter setting is outside of the valid setting range.
The same setting has been selected for two or more multi-function inputs
(H1-01, H1-02)
6.3 Operation Errors
53