YASKAWA CIMR-R5U23P71A Instruction Manual page 65

Power regenerative unit
Table of Contents

Advertisement

Setting Value
8
9
F
14
24-2F
Setting value
0
6
7
8
A
E
F
10
11
1E
1F
20
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
Table A.3 Multi-function Input Functions
Function
(H1-01, 02)
External baseblock (NO contact)
[Ext BaseBlk N.O.]
External baseblock (NC contact)
[Ext BaseBlk N.C.]
Not used
[Term Not Used]
Fault reset
[Fault Reset]
External fault
[External Fault]
Table A.4 Multi-function Output Functions
Function
(H2-02, 03)
During run
[During RUN 1]
Regenerative unit ready
[Regen Unit Ready]
During DC bus undervoltage (UV) detection
[DC Bus Undervolt]
During baseblock
[BaseBlk 1]
During MCON
[Mc On]
Fault
[Fault]
Not used
[Not Used]
Alarm
[Minor Fault]
Fault reset command active
[Reset Cmd Active]
Restart enabled
[Restart Enabled]
Overload (OL1) pre-alarm
[Overload (OL1)]
Overheat pre-alarm
[OH Prealarm]
24: External Fault, Normally Open, Always Detected, Coast To Stop
25: External Fault, Normally Closed, Always Detected, Coast To Stop
26: External Fault, Normally Open, During Run, Coast To Stop
27: External Fault, Normally Closed, During Run, Coast To Stop
28: External Fault, Normally Open, Always Detected, Fast Stop
29: External Fault, Normally Closed, Always Detected, Fast Stop
2A: External Fault, Normally Open, During Run, Fast Stop
2B: External Fault, Normally Closed, During Run, Fast Stop
2C: External Fault, Normally Open, Always Detected, Alarm Only
2D: External Fault, Normally Closed, Always Detected, Alarm Only
2E: External Fault, Normally Open, During Run, Alarm Only
2F: External Fault, Normally Closed, During Run, Alarm Only
Closed = When a run command is input or the Unit is outputting voltage.
Closed = When the Unit is powered up, not in a fault state, and in the DRIVE
Closed = When the DC bus voltage falls below the UV trip level set in L2-05.
Closed = When the Unit is not outputting voltage.
Closed = When the pre-charge contactor contact is energized.
Closed = When the Unit experiences a major fault.
Closed = When the Unit experiences an alarm.
Closed = When the Unit receives a reset command from a digital input terminal or
serial communication.
Closed = When the Unit is performing an automatic restart attempt. Automatic
restart is configured by parameter L5-01.
Closed = When OL1 is 80% of its trip point or greater.
Closed = When the Unit's heatsink temperature exceeds the setting of parameter
Remarks
Remarks
mode.
L8-02.
65