Parameter Name
Parameter
No.
Display
Language selection for operator
display
A1-00
[Select Language]
Parameter access level
A1-01
[Access Level]
Initialize
A1-03
[Init Parameters]
Password 1 (Input)
A1-04
[Enter Password]
Operation method selection
b1-02
[Run Source]
Read sequence input twice
b1-06
[Cntl Input Scans]
Automatic operation stop current
C8-17
[Autorun Iout]
Bias voltage at operation start
C8-18
[V Bias of Run]
Hysteresis voltage width at
operation start/stop
C8-19
[V Width of Stop]
Min. operating time
C8-20
[Minimum Run Time]
Excessive frequency deviation
detection level
F1-10
[FDEV DetectLevel]
Excessive frequency deviation
detection delay time
F1-11
[FDEV Detect Time]
Multi-function input (terminal S3)
H1-01
[Terminal S3 Sel]
Multi-function input (terminal S4)
H1-02
[Terminal S4 Sel]
Multi-function output (terminal M1-
M2)
H2-02
[Terminal M1 Sel]
Multi-function output (terminal M3-
M4)
H2-03
[Terminal M3 Sel]
62
Table A.2 Parameter List
Factory
Setting Range
Setting
Operation
0, 1
0
0 to 9999
4
0000 to 9999
0000
0000 to 9999
0
0, 1
1
0, 1
1
10 to 100%
50
0.0 to 50.0 V
2.0
0.5 to 50.0 V
3.0
0.0 to 600.0 sec
1.0
1.0 to 10.0 Hz
3.0
0.0 to 255.0 sec
70.0
0 to 2F
24
0 to 2F
14
0 to 20
6
0 to 20
0
Change
Access
during
Level
Language selection for the Digital Operator.
This parameter is not reset to the factory setting by
O
A
A1-03.
0: English
1: Japanese
Selects which parameters are accessible via the
Digital Operator.
O
A
0: Operation only
4: Advanced Level
Used to return all parameters to their factory or user
default settings. (Initializes and then returns A1-03 to
x
A
zero.)
2220: 2-Wire Initialization
When the value set into A1-04 does NOT match the
value set into A1-05, parameters A1-01 thru A1-03
cannot be changed. All other parameters as
x
A
determined by A1-01 can be changed. Parameter A1-
05 can be accessed by pressing the MENU key while
holding the RESET key.
Selects the run command input source.
0: Operator- RUN and STOP keys on Digital
x
A
Operator.
1: Terminals - Contact closure on terminals S1 or S2.
Sets the scan rate of terminals S1 to S4
x
A
0: 500 ms - 2 scans (for quick response)
1: 5 ms - 2 scans (for noisy environments)
x
A
For 400 V class power regenerative units, double the
x
A
initial setting and setting range.
For 400 V class power regenerative units, double the
x
A
initial setting and setting range.
x
A
Configures the frequency deviation fault (DEV)
detection. DEV fault will occur if the frequency
x
A
deviation is greater than the F1-10 setting for a time
longer than F1-11. F1-10 is set as a percentage of the
maximum output frequency (E1-04). Frequency
deviation is the difference between actual input
x
A
supply frequency and the frequency reference
command.
Selects the function of terminal S3.
24: External fault, Normally Open, Always Detected,
O
A
Coast To Stop.
Refer to
Selects the function of terminal S4.
14: Fault reset
O
A
Closed = Resets the Drive after the fault and the run
command have been removed.
Refer to
Selects the function of terminals M1 to M2.
6: Drive ready
O
A
Closed - When the Drive is powered up, not in a fault
state and in the DRIVE mode.
Refer to
Selects the function of terminals M2 - M4.
0: During Run 1
O
A
Closed - When a run command is input or the Drive
is outputting voltage.
Refer to
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
Description
Table
A.3.
Table
A.3.
Table
A.4.
Table
A.4.