Table A.1
shows the items that can be monitored in operation mode. The output signal levels for multi-function analog outputs shown in the table are
for a gain of 100.0 and a bias of 0.00.
Parameter
Parameter Name /
Function
No.
DC bus voltage
U1-02
DC Bus Voltage
AC power supply voltage
U1-04
AC Voltage
Current at power side
U1-05
AC Current
Power at power side
U1-07
AC Power
AC power supply frequency
U1-08
AC Frequency
Input terminal status
U1-10
Input Term Sts
Output terminal status
Status
Monitor
U1-11
Output Term Sts
Operation status
U1-12
Int Ct1 Sts 1
Cumulative operation time
U1-13
Elapsed Time
Software No.
U1-14
FLASH ID
Voltage deviation
U1-21
V Deviation
Software No. (CPU)
U1-28
CPU ID
60
Table A.1 Parameters Monitored in Operation Mode
Display
Monitors the DC voltage of the power regenerative unit's internal
main circuit
Monitors the AC power supply voltage.
Monitors the AC power supply current.
Monitors the AC power supply power.
Monitors the AC power supply frequency.
Shows input ON/OFF status.
Shows input ON/OFF status.
U1-10 =
<1 > : Can be selected by H1-01 or H1-02.
Shows output ON/OFF status.
U1-11 =
<2 > : Can be selected by H2-02 or H2-03.
Power regenerative unit operating status.
U1-12 =
Monitors the power regenerative unit's elapsed operating time.
Can be set with uparameter o2-07 or o2-08.
(Manufacturer's ID number)
Monitors the deviation between the AC power supply voltage and
the main circuit DC voltage.
(Manufacturer's ID number)
Function
00000000
1 : MANUAL RUN (terminal S1) ON
1 : AUTO RUN (terminal S2) ON
1 : EXFLT (terminal S3) ON <1>
1 : RESET (terminal S4) ON <1>
1 : Not used. (always 0)
00000000
0 : Not used. (always 0)
1 : Multi-function output 1
(terminals M1-M2) ON <2>
1 : Multi-function output 2
(terminals M3-M4) ON <2>
0 : Not used. (always 0)
1 : Fault output
(terminal MA/MB-MC) ON
00000000
1 : Running
0 : Not used. (always 0)
1 : Reset input ON
t
0 : Not used. (always 0)
1 : Power regenerative unit ready
0 : Minor fault detected
1 : Major fault detected
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
Output Signal Level for
Min.
Multi-function Analog
Unit
Outputs
200 V class: 400 V/10 V
400 V class: 800 V/10 V
(0 to +10 V Output)
200 V class: 200 V/5 V
400 V class: 400 V/5 V
(0 to +10 V Output)
Rated current /10 V
(0 to +10 V Output)
Rated power /10 V
1 kW
(0 to +10 V Output)
60 Hz /10 V
0.01 Hz
(0 to +10 V Output)
(Cannot be output)
200 V class: 400 V/10 V
400 V class: 800 V/10 V
(Cannot be output)
1 V
1 V
1 A
1 V