YASKAWA CIMR-R5U23P71A Instruction Manual page 57

Power regenerative unit
Table of Contents

Advertisement

Model CIMR-R5U
Heavy Duty
(See Note 2)
Rated
Capacity
Rating
Standard
Duty
(See Note 2)
Rated DC Current A
Regenerative Torque
Voltage Frequency
Input Power
Allowable Voltage Fluctuation
Supply
Allowable Frequency Fluctuation
Control Method
Control
Input Power Factor
Characteristics
Overload Capacity
Operation Input
Fault
Status Output
Running, READY Signal
Analog Output
Instantaneous Overcurrent
Blown Fuse
Overload
Undervoltage (DC Voltage)
Protective
Undervoltage (Power Side Voltage)
Function
Overload
Fin Overheat
Power Supply Open Phase
Power Frequency Error
Power Charge Indication
Location
Ambient Temperature
Environmental
Conditions
Humidity
Vibration
Note: Use a power regenerative unit with larger output capacity if the imbalance rate between phases exceeds 2%.
Note: <1> Imbalance rate between phases can be calculated using the following formula (Conforming to IEC1800-3). Imbalance rate between phases [%] = Three-phase
average voltage divided by (Max. voltage - Min. voltage) x 67.
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
Table 7.2 400 V Class Specifications
43P7
45P5
3
5
HP (kW)
(2.2)
(3.7)
Rated
Current on
4
6
Input Side
(100% Cont.)
5
7.5
HP (kW)
(3.7)
(5.5)
Rated
Current on
5
7.5
Input Side
(100%, 60s)
6
9
Heavy Duty: 100% cont., 125% for 60 s (25% ED), 187.5% for 30 s, max. torque < 250%
Standard Duty: 80% cont., 100% for 60s (25% ED), 150% for 30s, max. torque < 200%
47P5
4011
4015
4018
7.5
10
15
20
(5.5)
(7.5)
(11)
(15)
8
12
16
20
10
15
20
25
(7.5)
(11)
(15)
(18.5)
10
15
20
25
13
19
26
32
380 to 460 VAC 50/60 Hz,
+ 10 to - 15% (Imbalance rate between phases: within 2%) <1>
± 3 Hz (3 phase rotation)
120° current conduction
0.9 or more (Rated current)
Standard Duty: 150% for 30 seconds
Heavy Duty: 187.5% for 30 seconds
External terminals
1C contact output
Photocoupler output
Analog output: 1 point can be selected (current monitor)
Standard Duty: Stops at approx. 200% of the current on power side
Heavy Duty: Stops at approx. 250% of the current on power side
Motor stops by blown fuse.
Standard Duty: Stops after 30 seconds at 150% of rated current.
Heavy Duty: Stops after 30 seconds at 187.5% of rated current.
Stops at approx. 380 VDC or less.
Stops at approx. 300 VAC or less.
Stops at approx. 800 VDC or less.
Protected by thermistor
Stops at power supply open phase detection.
Stops by fluctuation more than ± 3 Hz of rated input frequency.
Indicated until main output voltage is approx. 50 V or less.
Indoor (Protected from corrosive gases and dust)
- 10°C to + 40°C (Closed wall–mounted)
- 10°C to + 45°C (Open chassis type)
90% RH or less (non–condensing)
9.8 m/s
2
(1G) less than 20 Hz, up to 1.96 m/s
4022
4030
4037
4045
25
30
40
50
(18.5)
(22)
(30)
(37)
24
32
40
48
30
40
50
60
(22)
(30)
(37)
(45)
30
40
50
60
37
51
64
77
2
(0.2G) at 20 to 50 Hz
4055
4075
60
75
(45)
(55)
60
80
75
100
(55)
(75)
75
100
96
128
57