2.2 Installation in hazardous location

CE-marked equipment
The CE mark symbolizes the compliance of the device with the following guidelines:
● EMC-guideline 89/336/EEC
● Low voltage guideline 73/23/EWG
● ATEX Directive 94/9/EG
● CT: (MI-001) Directive 2004/22/EC
2.2
Installation in hazardous location
Equipment used in hazardous locations must be Ex-approved and marked accordingly.
It is required that the special conditions for safe use provided in the manual and in the Ex
certificate are followed!
Ex approvals
CSA Class I, Division 2, Groups A, B, C and D. Code T5 for an ambient temperature of
+60 °C.
FM Class I, Division 2, Groups A, B, C and D and Class I, Zone 2, Group IIC indoor/outdoor
Type IP67 hazardous (classified) locations
Temperature specifications for Ex use
Temperature class
T2
T3
T4
T5
T6
EX requirements
It is required that:
● Electrical connections are in accordance with Elex V (VO in explosion hazardous areas)
● The protective cover over the power supply is properly installed. For intrinsically safe
12
WARNING
Ambient temperature [°C]
-40 to +40
180 (process temperature)
165 (process temperature)
100 (process temperature)
65 (process temperature)
50 (process temperature)
and EN60079-14 (Installing Electrical Systems in Explosion Hazardous Areas).
circuits the connection area can be opened.
-40 to +50
-
140 (process temperature)
100 (process temperature)
65 (process temperature)
50 (process temperature)
Operating Instructions, 12/2013, A5E02338368-002
-40 to +60
-
-
80 (process temperature)
65 (process temperature)
50 (process temperature)
SITRANS F M MAG 5000/6000