Current Output - Siemens SITRANS F M MAG 5000 Operating Instructions Manual

Electromagnetic flowmeters
Hide thumbs Also See for SITRANS F M MAG 5000:
Table of Contents

Advertisement

A.3

Current output

1)
2)
3)
SITRANS F M MAG 5000/6000
Operating Instructions, 12/2013, A5E02338368-002
If HART communication is installed, it is not possible to set the output for 0-20 mA (even
though the option is visible in the display). This is due to the fact that HART does not work if
the output falls below 2-3 mA.
4-20 mA + Alarm is the default setting for MAG 6000 I. For all other variants, the default setting
is 4-20 mA.
The controlling of alarm levels does not recognize if the jumper is mounted for passive output.
Do not combine differentiation and low alarm level together with passive output. The output will
try to pull down the level to 1.3 mA at fatal errors which is not possible for passive output.
Menu diagrams
A.3 Current output
77

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans f m mag 6000

Table of Contents