Figure 4-17 Normally-Open Repo Switch Wiring; Table 4-4. Normally-Open Repo Wire Terminations - Eaton 9EHD-33-40/20 User's Installation And Operation Manual

20-40 kva (380/400/415v)
Table of Contents

Advertisement

6.
7 .
Table 4-4 rePo Connections
Switch Contact Block
38
Eaton 9EHD UPS (20-40 kVA, 380/400/415V) Installation and Operation Manual
If required, install wiring from the REPO switch to the trip circuitry of the upstream protective devices. A
second contact block is provided on the REPO switch for this function . The REPO switch wiring must be in
accordance with local regulations.
Reinstall the interface terminal cover using the retained hardware.
from rePo Station(s)
To rePo Terminal Block
(either Block)
on Back of uPS Cabinet
3,4 NO
See Figure 4-13 for wiring
REPRO
Switch
(No)

figure 4-17 normally-open rePo Switch Wiring

Twisted Wires (2)
3
Twisted
Wires
4
Wire Size
Tightening Torque
7 lb in
(0.5 2.0 mm
-
)
(0.8 Nm)
2
1
2
REPO TB
3
4