Installing a rePo Switch

A latching-type Remote Emergency Power-off (REPO) switch can be used in an emergency to shut down the
UPS and remove power to the critical load from a location away from where the UPS is installed. Shows a
REPO switch.
To Install a REPO switch:
1.
Verify the UPS system is turned off and all power sources are removed. See Chapter 6, "UPS Operating
Instructions, " for shutdown instructions.
2.
Securely mount the REPO switch. Recommended locations include operator's consoles or near exit doors.
3.
To locate the appropriate terminals and review the wiring and termination requirements, see
paragraph 3.2.3, Table 4-3, Figure 4-6, Figure 4-8, and Figure 4-12.

Table 4-3 rePo Connections

rePo Terminal
4.
Normally-Open REPO Switch Wiring see Table 4-4 and Figure 4-13,Normally-Closed REPO Switch Wiring
seeTable 4-5 and Figure 4-14 .
5.
If using a normally-closed REPO switch, connect a jumper wire between pins 3 and 4 on the REPO terminal
block.
Before installing a REPO switch, verify that the UPS was installed according to the
NOTE 1
instructions in paragraphs 4.2 through 4.5.
When installing the REPO switch, you must install conduit between the device and
NOTE 2
the UPS cabinet for wiring the switch.
The REPO switch must be a normally-open or normally-closed latching-type switch
NOTE 3
not tied into any other circuits.
This procedure is intended for installing the Eaton-supplied REPO switch. If
NOTE 4
installing another manufacturer's switch, use this procedure, and Figure 4-13 and
Figure 4-14 as a guide.
The REPO switch wiring must be in accordance with local regulations.
NOTE 5
Normally Closed
REPO Contacts

figure 4-16 rePo Terminal Block Connector assignments

description
1
Input: normally-closed dry contact used to activate UPS EPO from a remote switch.
2
3
Input: normally-open dry contact used to activate UPS EPO from a remote switch.
4
uPS
Normally Open
REPO Contacts
Eaton 9EHD UPS (20-40 kVA, 380/400/415V) Installation and Operation Manual