SAFETY APPLICATION CONFIGURATION EXAMPLE (USING A
SINGLE SAFETY PROGRAMMABLE CONTROLLER)
Item
3. Time of noise removal filter X4, 5
5. Time of noise removal filter X8, 9
11. Doubling input discrepancy detection time X4, 5
13. Doubling input discrepancy detection time X8, 9
19. Input dark test selection X4, 5
21. Input dark test selection X8, 9
25. Input dark test pulse OFF time
40. Doubling/single input selection X4, 5
42. Doubling/single input selection X8, 9
46. Auto RTN Func to detect doubling input mismatch
5
5.6 Case Examples
- 43
5.6.4 Entering detection and existence detection circuit 2
For the light curtain and the mat switch, set the parameters as follows.
Table 5.21 CC remote (1) SR_IO1 parameter settings
*1
"1ms"
*1
"1ms"
*2
"20ms"
*2
"20ms"
"Not execute"
"Execute"
*1
"400 s"
*3
"Doubling input"
*3
"Doubling input"
*3
"Invalid"
*1:
Adjust the values of Time of noise removal filter and Input dark test pulse OFF time according to
the installation environment and wiring length.
*2:
Set Doubling input discrepancy detection time to 100ms for the mechanical switch and 20ms for
the sensor input as a standard.
*3:
The parameter is added to the QS0J65BTB2-12DT of technical version D.
When a module of technical version C or earlier is used, the parameter is not available.
*4:
For setting range, refer to the following.
CC-Link Safety System Remote I/O Module User's Manual
*5:
Always set the enclosed option for this case example.
*4*5