Mitsubishi Electric MELSEC-QS Series Safety Application Manual page 128

Safety programmable controller
Hide thumbs Also See for MELSEC-QS Series:
Table of Contents

Advertisement

5
SAFETY APPLICATION CONFIGURATION EXAMPLE (USING A
SINGLE SAFETY PROGRAMMABLE CONTROLLER)
Item
6. Time of noise removal filter XA, B
14. Doubling input discrepancy detection time XA, B
22. Input dark test selection XA, B
25. Input dark test pulse OFF time
27. Method of wiring of output Y1
31. Output dark test selection Y1
35. Output dark test pulse OFF time Y1
43. Doubling/single input selection XA, B
46. Auto RTN Func to detect doubling input mismatch
5
5.6 Case Examples
- 79
5.6.8 Two-hand operation switch
For the contactors, set the parameters as follows.
Table 5.36 CC remote (1) SR_IO1 parameter settings
*1
"1ms"
*2
"100ms"
"Execute"
*1
"400 s"
"Doubling wiring (Source+Sink)"
"Execute"
*1
"1ms"
*3
"Doubling input"
*3
"Invalid"
*1:
Adjust the values of Time of noise removal filter, Input dark test pulse OFF time, and Output dark
test pulse OFF time according to the installation environment and wiring length.
*2:
Set Doubling input discrepancy detection time to 100ms for the mechanical switch and 20ms for
the sensor input as a standard.
*3:
The parameter is added to the QS0J65BTB2-12DT of technical version D.
When a module of technical version C or earlier is used, the parameter is not available.
*4:
For setting range, refer to the following.
CC-Link Safety System Remote I/O Module User's Manual
*5:
Always set the enclosed option for this case example.
*4*5
Setting