P781 Data message

Note:
Applicable only to ports programmed for printer communication (parameter
770).
Sets the data message to be delivered via the selected port, ports 1 to 3 (P781-01 to -03).
All messages and printouts include time and date.
Entry:
f
0 = no message
1 = rate
2 = total*
3= rate and total*
4 = batch total (totalizer 5)
5 = quick start parameters (P001 – P017)
6 = all parameters
*totalizer 1 and/or 2 as set by P647, Totalizer Display
P799 Communications Control
Assigns programming control either locally through the keypad or Dolphin Plus (P770 = 1),
or remotely through Modbus protocol (P770 = 2 or 3) or SmartLinx ®
Entry:
0 = local
1 = remote
WARNING: When a SmartLinx
parameters that the SmarlLinx
be continuously updated. Therefore, if you connect a SmartLinx
card to the SF 500, set P799 = 1 and not write anything to the
SmarLinx
7ML19985CN01
®
card, your setpoints will be 0.
Milltronics SF 500 - INSTRUCTION MANUAL
.
®
card is installed and P799 = 1, the
®
card is writing to the SF 500 will
®
Page 75