LVDT

Standard
Red
Encapsulated
Red
maximum cable run LVDT to Conditioner 300 m (1000 ft.)
♦Shields are common, but not grounded to chassis. Run cable shields through SHLD
terminals and ground at SF 500 only.
If separation between the SF 500 and LVDT conditioner exceeds 150 m (500 ft.):
1.
remove the jumpers from SF 500 terminal 11/12 and 13/14
2.
run additional conductors from:
SF 500 terminal 12 to integrator terminal block '+EXC'
SF 500 terminal 13 to integrator terminal block '-EXC'
For further connection information on specific LVDTs consult Siemens Milltronics.
Note:
A common error is missing the connection from SF 500 terminal 2 to SF 500
terminal 17.
7ML19985CN01
EXC+
EXC-
Blue
Orange
flowmeter with
LVDT
Siemens Milltronics
SF 500
Milltronics SF 500 – INSTRUCTION MANUAL
COM
C.T.
Yellow
Black
White
Black
Siemens Milltronics LVDT Conditioner
SIG-
Green
Yellow
*
Page 11