9 = PID freeze
10 = PID setpoint source
11 = PID mode
12 = external alarm
13 = remote communication write
14 = Initiate On-line Calibration
15 = Accept new on-line calibration span**
Multispan
selection
1
2
3
4
5
6
7
8
*If the SF 500 is programmed for multispan operation, the auxiliary input contact state
determines the multispan number (equivalent to P365). Input 1 is reserved for multispan 1
and 2 selection. Input 2 is reserved for multispan 3 and 4 selection, and Input 3 for 5 to 8.
** Enter 1 (existing ALT_DSP) to reject the new on-line calibration span.
Calibration Parameters (P295 – 360)
P295
Load Cell Balancing
Initiates an electronic balancing of the load cell input signals. Balancing is required for
flowmeter models of two-load cell design.
Start Up
Refer to
P341
Days Of Service
The cumulative days that the application device has been in service. The time is recorded
once daily in a non-resetable counter. Periods of less than 24 hours. are not recorded, nor
f
accumulated. (
= 0)
Page 102
Auxiliary Input 1 Auxiliary Input 2 Auxiliary Input 3
on page 23 for requirements and execution.
Milltronics SF 500 - INSTRUCTION MANUAL
7ML19985CN01