Note:
To reset the Diagnostics relay, the SF 500 must be cycled between
PROGRAM and RUN mode
To reset the Batch relays, the Batch totalizer must be reset.
P101
High Alarm / Deviation Alarm
f
High Alarm (
= 100)
For relay functions P100 = 1: this parameter sets the high alarm setpoint for the relay
selected, relays 1 to 5 (P100 -01 to -05).
Enter the value in % of full scale.
Deviation Alarm (
For relay functions, P100 =3 and 4, this parameter sets the deviation setpoint for the relay
selected, relays 1 to 5 (P100 -01 to -05).
Enter the value in % of setpoint.
P102
Low Alarm
Sets the low alarm setpoint for relay selected, relays 1 to 5 (P100 - 01 to – 05). (
Enter the value in % of full scale
Note:
Not applicable if P100 = 2, 3, 4, 5, 6 or 7.
P107
Relay Alarms
Sets the alarm mode for the relay selected, relays 1 to 5 (P100 - 01 to - 05.
Entry:
f
1 = high and low
2 = high only
3 = low only
Note:
Not applicable if P100 = 2, 3, 4, 5, 6 or 7.
Page 96
f
= 10)
Milltronics SF 500 - INSTRUCTION MANUAL
f
= 20)
7ML19985CN01