display is programmed (P081) to scroll through rate, and totalization (P647), either
automatically, or by pressing the enter key.
Rate
Total 1
If the SF 500 is programmed for batch control, the batch display is added to the display
Batch Control (P560 - P568
scroll. Refer to
Access PROGRAM mode, zero and span calibration from RUN Mode.
PROGRAM mode allows viewing, and with security permission (P000), editing parameter
values. While in PROGRAM mode, RUN mode functions are still active, i.e.: rate, relay, mA
output and totalization. If PROGRAM mode is left idle for a period of ten minutes, the SF
500 automatically reverts to RUN mode.
Zero and span calibrations effectively halt RUN mode while they are in progress. During
this time, totalization ceases, and all mA outputs, except for PID, fall to zero.
Key
1
1
2
2
3
3
4 (EDIT Mode), Scroll Up (VIEW
4
Mode)
5
5
6
6
7
7
8 (EDIT Mode), Scroll Down
(VIEW Mode
8
9
9
0
0
Decimal Place
A
- (Dash)
M
Enter RUN Mode
RUN
PAR
Press either the ZERO key or the
ZERO
SPAN key to initiate Calibration
7ML19985CN01
becomes
PROGRAM Mode
Milltronics SF 500 – INSTRUCTION MANUAL
Rate
Total 2
Batching
on page 109 and
RUN Mode
Scroll Up through PID Local Set-
point and Manual Output Values
Scroll Down through PID Local
Setpoint and Manual Output Val-
ues
Print
Toggle between PID auto/manual
Enter PROGRAM Mode
Press either the ZERO key or the
SPAN key to initiate Calibration
on page 66.
Page 19