SF 500 and SmartLinx

In addition to three onboard communication ports, the SF 500 is compatible with Siemens
Milltronics SmartLinx ® communication modules which provide an interface to popular
industrial communication systems.
This section only describes the onboard communications. For more information on
SmartLinx ® , please consult the appropriate SmartLinx ® manual.
WARNING: When a SmartLinx
(Communications Control parameter), the parameters that the
SmartLinx
updated. Therefore, if you connect a SmartLinx
500, set P799 = 1 and not write anything to the SmartLinx
your setpoints will be 0.

Connection

There are three serial communication ports on the SF 500:
Port
1
2
3
Installation
Refer to

Wiring Guidelines

Improper wiring and choice of cables are the most common sources of communication
problems. Listed below are some suggested guidelines:
15 meters (50 feet) for RS-232
1200 meters (4000 feet) for RS-485
Ensure that communication cable is run separately from power and control cables
(i.e. do not tie wrap your RS-232 cable to the power cable or have them in the same
conduit).
cable is shielded and connected to ground at one end only
24 AWG (minimum)
follow proper grounding guidelines for all devices on the bus
use good quality communication grade (shielded twisted pairs) cable that is
recommended for RS-232.
Page 70
®
®
card is writing to the SF 500 will be continuously
Description
RS-232, Terminals 31 to 34
RS-485, terminals 41 to 46
RS-232, RJ-11 modular telephone jack
on page 6 for wiring diagrams specific to each port.
Milltronics SF 500 - INSTRUCTION MANUAL
®
card is installed and P799 = 1
®
card to the SF
®
card,
7ML19985CN01