Program the SF 500 as follows:
Parameter
P390 = 1
P391-01 = 30
P391-02 = 60
P391-03 = 90
P391-04 = 120
P391-05 = 150
P392-01 = - 10.7
P392-02 = 11. 1
P392-03 = - 5.1
P392-04 = 8.7
P392-05 = -6.0
Note:
Often only one point of compensation is required, usually at a low rate
value. In the prior example, if compensation was only required at 30 t/h, program
the following parameters. Optimize compensation by establishing the next rate
value that agrees with the material test, the compensation is zero and is entered
as the next compensation point.
P390 = 1
P391-01 = 30
P391-02 = 90
P392-01 = -10.7
P392-02 = 0
30
25
20
15
10
5
-10.7
0
0
30
Page 48
60
90
rate t/h
Milltronics SF 500 – INSTRUCTION MANUAL
Function
linearization ON
point 1, rate
point 2, rate
point 3, rate
point 4, rate
point 5, rate
point 1, compensation
point 2, compensation
point 3, compensation
point 4, compensation
point 5, compensation
linearization on
point 1, rate
point 2, rate
point 1, compensation
point 2, compensation
actual weight per material test
totalized weight by SF 500
flowmeter response
linearized SF 500 response
internal response 100% - 150% of span
% compensation
span (100%)
120
150
180
210
240
7ML19985CN01