P911
mA Output Test
Tests the mA output value for the output selected, outputs 1 to 3 (P911 -01 to -03)
Displays the value from the previous measurement. Enter a test value and the displayed
value is transmitted to the output. Upon returning to the RUN mode, the parameter
assumes the actual mA output level. (
Use the
and
P914
mA Input Value
Displays the current mA input value for the input selected, inputs 1 to 2 (P914 – 01 to -02).
Note:
Not applicable if mA I/O board is not connected.
P940
Load Cell mV Signal Test
Displays the raw (unbalanced) mV signal input for the selected load cell, load cells A to B
(P940 – 01 to – 02)
Range 0.00 - 50.00 mV.
P943
Load Cell A/D Reference
Displays the A/D reference value for the selected load cells. These values are affected by
load cell balancing (P295).
Load cells are:
– 01 = A and B
– 02 = A
– 03 = B
Note:
When using an LVDT it is displayed as input A.
P948
Error Log
Displays a log of the last 25 error or alarm events (P948 – 01 to – 25) that have occurred.
Event 01 is the current error.
Display:
0 = no error
# = error code; refer to
Page 116
f
= 0)
to scroll the value
Troubleshooting
Milltronics SF 500 - INSTRUCTION MANUAL
on page 118
7ML19985CN01