Starting up the CSL 710 with IO-Link interface
The configuration of an IO-Link interface involves the following steps on the receiver control panel and the
IO-Link master module of the control-specific configuration software.
The configuration described in the following is not necessary if you only use the switching out-
puts.
General prerequisites:
• The light curtain has been mounted (see chapter 6) and connected (see chapter 7) correctly.
• The basic configuration has been performed (see chapter 8).
9.1
Defining IO-Link configurations on the receiver control panel
The parameters for the IO-Link interface are configured with the configuration of the bit rate. By changing
the bit rate, the light curtain receives a new IO-Link device ID and must be operated with the compatible
IO Device Description (IODD).
NOTICE
Changes take effect immediately!
The changes become effective directly (without restart), but are not automatically stored in non-volatile
memory.
The IODD file is supplied with the device and is available for download at www.leuze.com.
Factory settings
• Bit rate (COM2) = 38.4 kbit/s
The bit rate is configurable
• Process data length (PD length) and process data content are defined as follows (not configurable):
16 bit PD: vccc cccc aaaa aaaa
• v: PD validity or status information
• c: Measurement cycle counter
• a: Switching state of beam areas 8 ... 1
The structure of this configuration in the receiver control panel menu is as follows:
Level 1
Commands
Operational setting
IO-Link
Select Main Settings > IO-Link > Bit rate.
The bit rate is configured.
Other possible configuration steps are performed via the
chapter 11).
Process mode is configured via the IO-Link master module of the control-specific software.
Leuze electronic
Level 2
Description
Teach
Filter depth
(enter value)
Beam mode
Parallel
Function reserve
High
Blanking teach
Not active
Power-Up teach
Not active
Smoothing
(enter value)
Bit rate
COM3: 230.4 kbit/s COM2: 38.4 kbit/s
Starting up the CSL 710 with IO-Link interface
Reset
Factory settings
Diagonal
Crossed-beam
Medium
Low
Active
Active
Sensor Studio
CSL 710
Exit
configuration software (see
55