Huawei NetCol5000-A User Manual page 258

42 kw air cooled in-row precision air conditioner
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
Menu
Parameter
Network port
Settings >
See
Comm
Settings >
SNMP Settings
Settings >
Action
Alarm Settings
Delay
Threshold
Settings >
T/H control type
System
Settings >
COMM Settings
Ctrl temp setpoint
at ctrl point
Ctrl humid
setpoint at ctrl
point
Cold-aisle sensor
Hot-aisle sensor
Heat
Issue 01 (2017-07-27)
Description
set to Client.
It is recommended that you retain the default
value 16100. If you need to change the value,
enter a value as required. This parameter is
configurable when Link mode is set to
Client.
4.5.7 Setting Communications Parameters (SNMP
Three options are available for setting
whether to report an alarm.
Enable: Alarms are reported to the EMS.
The LCD displays active alarms and the
system implements related protection
actions.
Disable: Alarms are not reported and no
protection actions are implemented.
Specifies the delay time for reporting alarms.
Specifies the alarm threshold for a certain
alarm.
Cold-aisle, Hot-aisle, Return-air, or
Supply-air can be set as required. The
temperature and humidity set points
correspond to the selected control type can be
set.
After the T/H control type and the
temperature value under this type are set, the
device conducts cooling or heating based on
the settings.
After the T/H control type and the humidity
value under this type are set, the device
conducts humidifying or dehumidifying based
on the settings.
The sensors in cold aisles can be set to
Enable or Disable.
The sensors in hot aisles can be set to Enable
or Disable.
Enable indicates that the electric heater will
be started when the ambient temperature is
lower than the certain temperature range of
the temperature set point. Disable indicates
that the electric heater will not be started.
Enabled when active pwr indicates that the
electric heater will be started when the main
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
C Parameter Description
Default Value
16100
Parameters).
Allow
Not displayed
Not displayed
Return-air
23.0° C
50.0%RH
Disable
Disable
Enable
250