Huawei NetCol5000-A User Manual page 26

42 kw air cooled in-row precision air conditioner
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
Table 2-6 Optional specifications
Item
Power
system
Power
supply
mode
Max
Current
Condensa
te pump
Heating
function
Humidifi
cation
function
Reheating
capacity
Humidify
ing
capacity
Table 2-7 Application conditions
Operating
temperature
Operating
temperature
Operating
humidity
Storage
temperature
Storage
humidity
Applicable
outdoor
temperature
Issue 01 (2017-07-27)
NetCol5000-A0
NetCol5000-A0
42H413D20020
42H413D20020
E1
E2
380–415 V AC, 50 Hz or 60 Hz 3Ph+N+PE
Tolerance: –10% to +10% of rated voltage, rated frequency± 3 Hz
Single power
Dual power
supply
supplies
40 A
Active: 40 A
Standby: 40 A
Yes
Yes
No
No
No
No
N/A
N/A
N/A
N/A
Specifications
18–45° C
20%–80% RH
–40° C to +70° C
5%–95% RH (non-condensing)
Work with NetCol500-A0365C (including a low-temperature
component): –40° C to +45° C
Work with NetCol500-A0365S: –20° C to +45° C
Work with NetCol500-A072: –5° C to +55° C
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2 Product Description
NetCol5000-A0
NetCol5000-A0
42H413D2W12
42H413D2W12
0E1
0E2
Single power
Dual power
supply
supplies
46 A
Active: 46 A
Standby: 40 A
Yes
Yes
Yes
Yes
Yes
Yes
6 kW
6 kW
3 kg/h
3 kg/h
18