NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
Figure 5-32 Removing a condensate pump assembly
1.
2.
Step 4 Remove the hose clamps on the condensate pump pipes and the condensate pump using a
flat-head screwdriver, pull out the hose, and take out the condensate pump, as shown in
Figure
Figure 5-33 Removing a condensate pump
Issue 01 (2017-07-27)
Remove the hose clamp at the water pan drain outlet, and remove the hose, as shown by
(1) and (2) in
Figure
5-32.
Remove the three screws that secure the condensate pump assembly using a socket
wrench, and pull out the condensate pump assembly, as shown by (3) in
5-33.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Operation and Maintenance
Figure
5-32.