Huawei NetCol5000-A User Manual page 80

42 kw air cooled in-row precision air conditioner
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
Figure 3-44 Securing a differential pressure sensor
Step 2 Connect a pressure inlet tube to the + mark on the micro differential pressure sensor and route
it to the cold aisle through the hole on the top of the cabinet. Connect another pressure inlet
tube to the – mark on the micro differential pressure sensor and route it to the hot aisle
through the hole on the top of the cabinet, as shown in step 2 in
Step 3 Connect the three terminals of 12 V DC, GND, and 0-5 V feedback of differential pressure
sensor cable to ports 1, 2, and 3 (from left to right) on the X303 terminal, as shown in
3-45.
Figure 3-45 Connecting a differential pressure sensor
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Installation Guide
Figure
3-44.
Figure
72