NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
Figure 5-26 Liquid level detector
(1) High liquid level detector
Procedure
Step 1 On the controller home screen, tap Shutdown, and turn off the air conditioner switch in the
PDC.
Exercise caution because the device is still energized after it is shut down on the controller
home screen.
Step 2 Open the front door, and remove the water pan cover, as shown in
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Operation and Maintenance
(2) Low liquid level detector
Figure
5-27.
179