Huawei NetCol5000-A User Manual page 40

42 kw air cooled in-row precision air conditioner
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
Installati
on
Scenario
Outdoor
unit
Indoor
and
outdoor
units
Teamwork
control
Issue 01 (2017-07-27)
Item
Specifications
OT
Naked crimping terminal, OT, 10
2
terminal
mm
, M6, 60 A, tin plating, naked
ring terminal
Cord end
Common terminal, single cord end
terminal
terminal, conductor cross section 10
2
mm
, length 22 mm, 50 A, insertion
depth 12 mm, ivory
Power
Electrical power cable, 600 V/1000
cable
V, ZA-RVV, 5 x 2.5 mm
(optional)
(five cores: brown, black, gray, blue,
and yellow/green), 27 A, outdoor
cable, CE
OT
Naked crimping terminal, OT, 2.5
2
terminal
mm
, M6, 27 A, tin plating, 16–14
AWG, blue
Cord end
Naked crimping terminal, single-wire
terminal
cord end terminal, 2.5 mm
tin plating, insertion depth 8 mm,
blue
Signal
Electrical power cable, 300 V, SJTW,
cable to
3 x 16 AWG, black (three cores:
the indoor
black, white, and green), 10 A,
and
shielded outdoor cable, UL
outdoor
units
(optional)
Signal
Electrical power cable, 450 V/750 V,
cable to
H07RN-F, 2 x 1 mm
the indoor
cores: brown and blue), 10 A, rubber
and
power cable, VDE
outdoor
units
(optional)
Cord end
Naked crimping terminal, single-wire
terminal
cord end terminal, 1.5 mm
for the
tin plating, insertion depth 8 mm, red
cable
Teamwork
Symmetric twisted-pair cable, 100
control
ohm, enhanced category 5 cable,
network
aluminum foil shield, 0.52 mm, 24
cable
AWG, eight cores, four pairs of
(optional)
PANTONE 430U, equipped with
plug
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Remarks
supply: 1 PCS
Delivered with the
fittings
Delivered with the
fittings
The length is
2
, black
determined based on
site survey.
Delivered with the
fittings
Delivered with the
2
, 12.5 A,
fittings
The cable applies to the
RS485 communication
connection. The length
is determined based on
site survey.
The cable applies to the
2
, black (two
dry contact connection.
The length is
determined based on
site survey.
Delivered with the
2
, 7.5 A,
fittings
1 PCS (10 m)
3 Installation Guide
32

Hide quick links:

Advertisement

Table of Contents
loading