NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
Step 3 Disconnect cables from the RS485_IN and RS485_OUT ports on the T/H sensor, as shown by
(1) in
Step 4 Pull out the T/H sensor in the direction shown by (2) in
Figure 5-53 Removing a T/H sensor
Before installing a new T/H sensor, check that the DIP switch setting is consistent with that for the
original T/H sensor.
Step 5 Connect cables to the RS485_IN and RS485_OUT ports, and install a new T/H sensor in the
original position.