Huawei NetCol5000-A User Manual page 193

42 kw air cooled in-row precision air conditioner
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
Step 5 Install the new condensate pump and reinstall the condensate pump assembly in the cabinet.
Connect the water pipe and secure it using hose clamps. Connect the condensate pump power
cable.
Figure 5-34 Installing a condensate pump
Step 6 Remove the blockage from the pipe and close the front door.
Step 7 Power on the device. On the LCD home screen, choose Maint > Performance Maint, and
clear the condensate pump runtime.
Figure 5-35 Performance maintenance
Step 8 Tap Startup on the home screen. Ensure that the air conditioner is running normally without
any alarms.
----End
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Operation and Maintenance