Huawei NetCol5000-A User Manual page 92

42 kw air cooled in-row precision air conditioner
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
Figure 4-2 Vacuumizing the system with a low-temperature component
(1) Vacuum pump
(4) Low-pressure needle
valve
Step 2 In the beginning, the vacuum pump makes loud noise and exhausts white smoke from the
exhaust vent. After 10 minutes, if it still exhausts white smoke, observe it for another 10
minutes because the cooling system may not be sealed properly or there may be too much
refrigerant or water residues in the cooling system.
Step 3 After 20 minutes, the pressure gauge pointer should be in the negative area and the vacuum
pump makes small noise. Close and open the pressure gauge alternatively for several times.
The position of the pressure gauge pointer and the sound made by the vacuum pump do not
obviously change. Otherwise, the cooling system may not be sealed properly.
Step 4 Vacuumize the cooling system for at least 80 minutes after checking that the cooling system
does not leak. The pressure displayed on the vacuum pump should be less than or equal to 60
Pa (absolute pressure). When the pressure stops dropping, pump for another 10 minutes. The
indication of sight glass is dry (green).
Step 5 Close all the pressure gauge valves, and the vacuum pump after vacuumizing the cooling
system. Preserve the pressure for 10 minutes without disconnecting the connection. The
pressure should be lower than and equal to 90 Pa (absolute pressure).
Issue 01 (2017-07-27)
If a low-temperature component is installed on the outdoor side, connect the pressure
gauge and vacuum pump at the low-pressure, discharge pipe, and liquid pipe needle
valves to vacuumzie the system simultaneously, as shown in
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
(2) Pressure gauge 1
(5) Exhaust pipe needle
valve
4 Commissioning
Figure
4-2.
(3) Pressure gauge 2
(6) Liquid pipe needle
valve
84

Hide quick links:

Advertisement

Table of Contents
loading