Wsk-Link™ - Master/Slave Connection; Network - Window Master MotorController WCC 310 UL Installation Instructions Manual

Plus versions
Hide thumbs Also See for MotorController WCC 310 UL:
Table of Contents

Advertisement

WSK-Link™ - master/slave connection
The WSK-Link™ connection between to MotorControllers is done via input X5 or X6 on the master and input X11 on the slave.
A MotorController can have a master/slave connection to several MotorControllers. However, the total max number of
connected slaves on the bus must not exceed 10 units.
The total cable length must not exceed 200m, see S1 X11 for examples for connection of MotorControllers.
A slave can only have one master, whereas a master can have several slaves and a MotorController can both be a slave and a
master to MotorControllers.
A connected slave MotorController is shown on
the master MotorController's touch screen.
The slave MotorController's appearance on
the master MotorController

Network

For configuring network addresses.
The WCA 3CP card has a 10/100Mbit Ethernet connection. The connection support DHCP or static IP address as well as
Gateway
The appendix contains all the items that can be configured - see appendix for detailed explanation.
Network is used in with BACnet IP interface – contact WindowMaster for further information.
Sequence control configuration – motor line
1. Sequential control position limit
2. Sequential control with (upon what should the motor line wait?)
3. Sequential control with No
4. Sequential control position logic
Configuration of Master – Slave system:
When two MotorControllers are connected to each other in a
master-slave connection, the slave will appear as a green break
glass unit on the master's touch screen.
On the master's touch screen the Device type of the slave will
appear as a WCC 3xx.
WCC 3XX
the max position the motor line is allowed to have without the
„result" is being fulfilled.
®
For MotorLink
motor lines stepless variable.
For ±24 Volt motor lines 0 or 100%
1. Motor line.
2. Local input
3. The state of a KNX object
4. The state of a BACnet object
Upon which number should the motor line wait
In which positions should the sequential control be active
32