Motor line card – WCA 3M4 / WCA 3M8
The motor line cards WCA 3M4
and WCA 3M8, allows
connection of additional 4 and 8
motor lines respectively either
±24V standard or MotorLink
The WCA 3M4 / WCA 3M8 is
connected to
WCA 3CP via a CAN-cable (J3
on WCA 3M4 / WCA 3M8 and
J4 on the WCA 3CP).
S2
For connection of ±24 Standard actuators or MotorLink
X1 - X8
Data:
x.1 24V / 0V
x.2 ML Communication
x.3 0V / 24V
For actuator connections, please see explanation in section "WCA 3CP main control card" under "X1 / X2" and
"Max number of actuators per card".
F1 - F8
3.15A fuse for motorline (WCA 308)
J3
Connection to main control card (WCA 3CP)
J4
Power connection from control card (WCA 3CP)
J6
Connection to input card (WCA 3KI)
J7
Power supply control
®
®
actuators.
21