Configuration of the sensor
Sequence control
The sequence control functionality is used where the movement of a motor line must depend on an external event or
situation/stage.
To be used where window flabs are overlapping or where the windows cannot open (more than 15%) if the blinds are down a.s.o.
The sequence control can be controlled depending on;
- the position of a different motor line
- the state of a local input
- the state of a KNX object
- the state of a BACnet object
Activation of sequence control
Sequence control configuration
Weather shall be configured in:
None
(no configuration)
WOW
1.
Filter constant
2.
Slow filter constant
3.
Use RMS in filter
The appendix contains all the items that can be configured - see
appendix for detailed explanation.
WLA
1. Pulses/sec. per m/s
2. Filter constant
3. Slow filter constant
4. Use RMS in filter
The appendix contains all the items that can be configured - see
appendix for detailed explanation.
From WSK Link™
(no configuration)
Sequence control configuration
The activation of sequence control is to be done for each motor line.
The function for the sequence control is to be configured for each
motor line
1. None - This motor line does not use sequence control
2. Open - This motor line must wait for a "result" before opening
3. Close - This motor line must wait for a "result" before closing
31