Even though the connecting method of MotorControllers shown in the #2 example, enables a physical larger
system, with longer distances between MotorControllers, WindowMaster recommends connecting the master
slave MotorControllers as shown in example #1. As only the master sends e.g. smoke commands and slaves
only respond to commands received from the master, the response time in example 2 is heavily increased in
comparison with the response time in example 1.
F2 - F3
3.15A fuse for motorline (WCA 308)
J1
Connection for power supply
J2
Power to motor line card (WCA 3M4 / WCA 3M8)
Connection to AUX (WCA 3P6) – 120V supply
J3
J4
Connection for motor line card (WCA 3M4 / WCA 3M8)
J7
2 x Ethernet connection
J8
USB host. Used to store configurations and to start an event log for e.g. trouble shooting
J9
USB device. Used for remote control and to flash the MotorController.
J10
Connection for fieldbus card
P1
Power supply control
R / P
Reset / programming (used for firmware updates)
Shows the status of the MotorController
Yellow = fault, flashing yellow = service timer expired, time for service
LED
Green fast flickeing = CPU working, Green constant = CPU communication stopped (possible reset or contact
WindowMaster)
↓ ↑
Close / open all windows