Variable Area (Setting Range) List - Omron E5CC Communications Manual

Digital temperature controllers. e5*c series
Hide thumbs Also See for E5CC:
Table of Contents

Advertisement

3 Communications Data for CompoWay/F
3-1

Variable Area (Setting Range) List

• For communications using a variable type not enclosed in parentheses in the following table, the set
value is double-word data (8 digits). For communications using a variable type enclosed in
parentheses, the set value is single-word data (4 digits).
• For example, variable type C0 is double-word data (8 digits), and variable type 80 is single-word data
(4 digits).
• Items expressed in hexadecimal in the "Setting (monitor) value" column are the setting range for
CompoWay/F communications. The values in parentheses are the actual setting range. When there
is a section reference for a setting item, refer to that reference for details.
Variable
Address
type
C0 (80)
0000
C0 (80)
0001
C0 (80)
0002
C0 (80)
0003
C0 (80)
0004
C0 (80)
0005
C0 (80)
0006
C0 (80)
0007
C0 (80)
0008
C0 (80)
0009
C0 (80)
000A
C0 (80)
000B
C0 (80)
000C
C0 (80)
000E
C0 (80)
0011
C0 (80)
0012
C0 (80)
0013
*1
Not displayed on the Controller display.
*2
When the variable type is 80 (word access), the rightmost 16 bits are read.
*3
When the variable type is 80 (word access), the leftmost 16 bits are read.
*4
You can use this selection only with the E5EC-PR@-8@@ or E5AC-PR@-8@@. (The Digital Controller must
be manufactured in August 2014 or later (version 2.2 or higher).)
3 - 2
Parameter name
PV
Temperature: Use the specified range for each sensor.
Analog:
Refer to 3-2 Status and Status 2 for details.
*1*2
Status
SP lower limit to SP upper limit
*1
Internal Set Point
Heater Current 1
H'00000000 to H'00000226 (0.0 to 55.0)
Value Monitor
MV Monitor
Standard:
(Heating)
Heating and cooling: H'00000000 to H'0000041A
MV Monitor
H'00000000 to H'0000041A (0.0 to 105.0)
(Cooling)
Heater Current 2
H'00000000 to H'00000226 (0.0 to 55.0)
Value Monitor
Leakage Current 1
H'00000000 to H'00000226 (0.0 to 55.0)
Monitor
Leakage Current 2
H'00000000 to H'00000226 (0.0 to 55.0)
Monitor
Soak Time Remain
H'00000000 to H'0000270F (0 to 9999)
Valve Opening
H'FFFFFF9C to H'0000044C (−10.0 to 110.0):
Monitor
Measured opening
H'00000000 to H'000003E8 (0.0 to 100.0): Estimated
opening
Remote SP Monitor Remote SP lower limit −10%FS to Remote SP upper
limit +10%FS
Multi-SP No.
H'00000000 to H'00000007 (0 to 7)
Monitor
Decimal Point
H'00000000 to H'00000003 (0 to 3)
*1
Monitor
Refer to 3-2 Status and Status 2.
*1*2
Status 2
Refer to 3-2 Status and Status 2.
*1*3
Status
Refer to 3-2 Status and Status 2.
*1*3
Status 2
Setting (monitor) value
Scaling lower limit −5% FS to Scaling
upper limit +5% FS
H'FFFFFFCE to H'0000041A
(−5.0 to 105.0)
(0.0 to 105.0)
*4
E5@C Digital Temperature Controllers Communications Manual (H175)