Omron E5CC Communications Manual page 108

Digital temperature controllers. e5*c series
Hide thumbs Also See for E5CC:
Table of Contents

Advertisement

5 Communications Data for Modbus
Address
Parameter name
Four-byte
Two-byte
mode
mode
0E48
2E24
Extraction of Square Root
Enable
0E60
2E30
Travel Time
0F00
2F00
Alarm 1 Type
0F02
2F01
Alarm 1 Latch
0F04
2F02
Alarm 1 Hysteresis
0F06
2F03
Alarm 2 Type
0F08
2F04
Alarm 2 Latch
0F0A
2F05
Alarm 2 Hysteresis
0F0C
2F06
Alarm 3 Type
0F0E
2F07
Alarm 3 Latch
0F10
2F08
Alarm 3 Hysteresis
0F12
2F09
Alarm 4 Type
0F14
2F0A
Alarm 4 Latch
0F16
2F0B
Alarm 4 Hysteresis
0F18
2F0C
Standby Sequence Reset
0F1A
2F0D
Auxiliary Output 1 Open
in Alarm
5 - 12
Setting (monitor) value
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000001 to H'000003E7 (1 to 999)
H'00000000 (0): Alarm function OFF
H'00000001 (1): Upper and lower-limit alarm
H'00000002 (2): Upper-limit alarm
H'00000003 (3): Lower-limit alarm
H'00000004 (4): Upper and lower-limit range alarm
H'00000005 (5): Upper and lower-limit alarm with standby sequence
H'00000006 (6): Upper-limit alarm with standby sequence
H'00000007 (7): Lower-limit alarm with standby sequence
H'00000008 (8): Absolute-value upper-limit alarm
H'00000009 (9): Absolute-value lower-limit alarm
H'0000000A (10): Absolute-value upper-limit alarm with standby
sequence
H'0000000B (11): Absolute-value lower-limit alarm with standby
sequence
H'0000000C (12): LBA (Loop Burnout Alarm)
H'0000000D (13): PV change rate alarm
H'0000000E (14): SP absolute-value upper-limit alarm
H'0000000F (15): SP absolute-value lower-limit alarm
H'00000010 (16): MV absolute-value upper-limit alarm
H'00000011 (17): MV absolute-value lower-limit alarm
H'00000012 (18): RSP absolute-value upper-limit alarm *
H'00000013 (19): RSP absolute-value lower-limit alarm *
*
Valid only with a remote SP input.
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
H'00000000 to H'00000013 (0 to 19)
Note: Same settings as the Alarm 1 Type. However, the LBA (loop
burnout alarm) cannot be set.
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
H'00000000 to H'00000013 (0 to 19)
Note: Same settings as the Alarm 1 Type. However, the LBA (loop
burnout alarm) cannot be set.
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
H'00000000 to H'00000013 (0 to 19)
Note: Same settings as the Alarm 1 Type. However, the LBA (loop
burnout alarm) cannot be set.
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
H'00000000 (0): Condition A
H'00000001 (1): Condition B
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
E5@C Digital Temperature Controllers Communications Manual (H175)
Level
Initial setting
Advanced
function
setting
Initial setting
Advanced
function
setting
Initial setting
Advanced
function
setting
Initial setting
Advanced
function
setting
Initial setting
Advanced
function
setting

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5ecE5cc-uE5acE5dcE5gc

Table of Contents