Omron E5CC Communications Manual page 99

Digital temperature controllers. e5*c series
Hide thumbs Also See for E5CC:
Table of Contents

Advertisement

Address
Parameter name
Four-byte
Two-byte
mode
mode
0500
2500
Operation/Adjustment
Protect
0502
2501
Initial
Setting/Communications
Protect
0504
2502
Setting Change Protect
0506
2503
PF Key Protect
0508
2504
Move to Protect Level
050A
2505
Password to Move to
Protect Level
050C
2506
Parameter Mask Enable
050E
2507
Changed Parameters
Only
0600
2600
Manual MV
0602
2601
Set Point
0604
2602
Remote SP Monitor
0608
2604
Heater Current 1 Value
Monitor
060A
2605
MV Monitor (Heating)
060C
2606
MV Monitor (Cooling)
060E
2607
Valve Opening Monitor
*
You can use this selection only with the E5EC-PR@-8@@ or E5AC-PR@-8@@. (The Digital Controller must be
manufactured in August 2014 or later (version 2.2 or higher).)
E5@C Digital Temperature Controllers Communications Manual (H175)
5 Communications Data for Modbus
Setting (monitor) value
H'00000000 (0):
No restrictions in operation and adjustment levels
H'00000001 (1):
Move to adjustment level is prohibited.
H'00000002 (2):
Display and change of only "PV" and "PV/SP"
parameters is allowed.
H'00000003 (3):
Display of only "PV" and "PV/SP" parameters is
allowed.
H'00000000 (0):
Move to initial setting/communications setting
level is allowed. (Move to advanced function
setting level is displayed.)
H'00000001 (1):
Move to initial setting/communications setting
level is allowed. (Move to advanced function
setting level is not displayed.)
H'00000002 (2):
Move to initial setting/communications setting
level is prohibited.
H'00000000 (0): OFF (Changing of setup on controller display is
allowed.)
H'00000001 (1): ON (Changing of setup on controller display is
prohibited.)
H'00000000 (0): OFF
H'00000001 (1): ON
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFF831 to H'0000270F (−1999 to 9999)
(Can only be set. The monitor value is always H'00000000.)
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF
H'00000001 (1): ON
Standard Models
Standard control:
H'FFFFFFCE to H'0000041A (−5.0 to 105.0)
Heating and cooling control:
H'FFFFFBE6 to H'0000041A (−105.0 to 105.0)
Position-proportional Models
Close position-proportional control with the Direct Setting of
Position Proportional MV parameter set to ON:
H'FFFFFFCE to H'0000041A (−5.0 to 105.0)
SP lower limit to SP upper limit
Remote SP lower limit −10% FS to Remote SP upper limit +10% FS
H'00000000 to H'00000226 (0.0 to 55.0)
Standard control:
H'FFFFFFCE to H'0000041A
(−5.0 to 105.0)
Heating and cooling control:
H'00000000 to H'0000041A
(0.0 to 105.0)
H'00000000 to H'0000041A (0.0 to 105.0)
H'FFFFFF9C to H'0000044C (−10.0 to 110.0): Measured opening
H'00000000 to H'000003E8 (0.0 to 100.0): Estimated opening*
Level
Protect
5
Manual
control
Operation
5 - 3

Hide quick links:

Advertisement