PLC, an error will occur in the PLC. (An error code will be set in the Response Flag in PLC memory.) If
you cycle the power supply to the E5@C or move to the initial setting level and then go back to the oper-
ation level, the Communications Writing parameter will automatically change to ON.
6-2-11 Communications Monitor Parameter
This parameter displays the communications cycle time of the E5@C. If communications with the PLC
are not possible, c.err is displayed and then the cycle time is displayed again when communications
are restored.
E5CC
No.0
C
25
0
Adjustment Level
Display condition: The Protocol Setting parameter must be set to fins, mcp4, or fxp4.
Parameter name
Communications
Monitor
Note: If this parameter is monitored in PLC memory, the cycle time is given as 0 to FFFF hex (0 to 65,535
decimal). An error is indicated by FFFF hex.
E5@C Digital Temperature Controllers Communications Manual (H175)
PLC
E5CC
E5CC
No.1
No.2
C
C
C
25
0
Cycle time of E5CC with communications unit number 0
Displayed
characters
Normal operation: 0 to 9999 ms. If 9,999 ms is exceeded,
plcm
]]]] is displayed.
Error: c.err
6 Programless Communications
E5CC
No.0
C
C
25
25
25
25
0
0
0
0
Monitor range*
Order of
communications
Default
---
6