(4) We will change the set point for the No. 0 Controller.
Double-click D17 (Set Point) in the Device Memory Dialog Box, enter 100 (64 hex) for the
value, click the Set Button, and then click the Close Button. Confirm that D0 (Request Flag)
remains at 1 (Enable Writing) and that the SV Display on the No. 0 Controller changes to
100.
Confirm this for the No. 1 and No. 2 Controllers as well.
Stopping the E5CC Controllers
(1) We will run the No. 0 Controller.
Change the RUN/STOP parameter (r-s) in the operation level of the E5CC to RUN (run).
For a Controller with event inputs, the Event Input 2 Assignment parameter (ev-2) in the
initial setting level is set to RUN/STOP (stop), so the RUN/STOP parameter will not be dis-
played. Change the Event Input 2 Assignment parameter to NONE (none), and then
change the RUN/STOP parameter to RUN.
(2) We will switch the No. 0 Controller to STOP.
In the Device Memory Dialog Box, make sure that D15 (Request Flag) is 1 (Enable Writing)
and then double-click D16 (Operation Command Code). Select the HEX Option, enter 0101
hex (STOP), click the Set Button, and then click the Close Button. D16 will change to 0, D0
(Response Flag) will remain at 1 (Enable Writing), and "STOP" will be displayed on the No.
0 Controller. Confirm this for the No. 1 and No. 2 Controllers as well. For details on other
operation command codes, refer to 6-3-4 Operation Command Codes.
E5@C Digital Temperature Controllers Communications Manual (H175)
6 Programless Communications
6
6 - 65