A
Technical appendix
Fieldbus
Status information
– Protocol
– Version
– CC-Link chip
– Vendor code
– Machine type
Transmission rates
(The maximum permitted fieldbus length de
pends on the baud rate used, è section 2.5.2)
Coupling and uncoupling during operation
Cable type
– Reference cable (KURAMO ELECTRIC Co., Ltd.)
– Alternative (DYDEN Corporation)
– Alternative (LEONI protec cable Systems
GmbH)
– Terminating resistor
A.2
Default parameterisation
Note
The following tables contain an overview of parameters of the bus node. The current
and detailed description of all parameters of a CPX terminal are found in the CPX system
description (P.BE-CPX-SYS-...) as well as in the description of each CPX module.
System parameters
Monitoring
– Short circuit/overload in sensor supply (SCS)
– Short circuit/overload at the outputs (SCO)
– Undervoltage at the outputs (U
– Undervoltage at valves (U
– Short circuit at valves (SCV)
Force mode
Defines whether the Force function is blocked glob
ally or enabled.
System start
Defines the starting reaction of the CPX terminal.
Saves current parameter settings.
Tab. A.1
System parameters
78
CC-Link
Version 1.1 and 2.0
MFP3
0x0177
0x3C
156 kBd, 625 kBd, 2,5 MBd, 5 MBd, 10 MBd
Yes (online-return function, slave station cut-off
function)
Cable specification (è Section 2.5.1)
FANC-110SBH, 20 AWG × 3
CC-110, CC-110-5, CS-110, CM-110-5, 20 AWG × 3
L45467-Y19-C15, 20 AWG × 3
110 Ω / 0.5 W
)
OUT
)
VAL
Function no.
4401
4402
4402
Festo – P.BE-CPX-FB23-24-EN – 1411b – English
Default setting
active
active
active
active
active
blocked
System start with de
fault parameterisation
(factory setting) and
current CPX expansion.