1-2
Chapter 1: Module Overview
Section 1.2
Input Types
Section 1.3
Data Formats
User's Manual Pub. 0300266-02 Rev. B
The IF4U module supports the following input types.
Table 1-1. Input Types
Input Type
E Type Thermocouple
J Type Thermocouple
K Type Thermocouple -270 to 1370 ˚C (-454 to 2498 ˚F)
T Type Thermocouple
100 Ω Pt α 0.385
1000 Ω Pt α 0.385
100 Ω Pt α 0.3916
1000 Ω Pt α 0.3916
Resistance
Voltage
Current
CJC
For each channel, the data can be configured for:
•
Engineering Units ×1
•
Engineering Units ×10
•
Scaled-for-PID
•
Raw/proportional counts
Range
-270 to 1000 ˚C (-454 to 1832 ˚F)
-210 to 1200 ˚C (-346 to 2192 ˚F)
-270 to 400 ˚C (-270 to 752 ˚F)
-200 to 850 ˚C (-328 to 1562 ˚F)
-200 to 850 ˚C (-328 to 1562 ˚F)
-200 to 630 ˚C (-328 to 1166 ˚F)
-200 to 630 ˚C (-328 to 1166 ˚F)
0 to 3000 Ω
±50 mV
±100 mV
±1 V
0 to 5 V
1 to 5 V
±10 V (IF4U)
4 to 20 mA
0 to 20 mA
-25 ˚C to 85 ˚C
Need help?