Input
Thermocouple Inputs
CJC profile accuracy
CJC Sensor resolution
CJC Sensor accuracy
Voltage Inputs
Appendix A: Module Specifications
Specification
Linearization per ITS-90, The limits do not include the cold junction
compensation or thermocouple sensor errors.
System accuracy at 25 °C (Using 4 Hz and 17 Hz filters)
Type J: ±0.6 °C maximum
Type T (-190 °C to 400 °C): ±1 °C maximum
Type T (-270 °C to -190 °C): ±7 °C maximum
Type K (-200 °C to 1370 °C): ±1 °C maximum
Type K (-270 °C to -200 °C): ±10 °C maximum
Type E (-200 °C to 1000 °C): ±0.6 °C maximum
Type E (-270 °C to -200 °C): ±5 °C maximum
System accuracy at 0 °C to +55 °C (Using 4 Hz and 17 Hz filters)
Type J ±1.2 °C maximum
Type T (-190 °C to 400 °C): ±2 °C maximum
Type T (-270 °C to -190 °C): ±14.0 °C maximum
Type K (-200 °C to 1370 °C): ±2 °C maximum
Type K (-270 °C to -200 °C): ±20 °C maximum
Type E (-200 °C to 1000 °C): ±1.2 °C maximum
Type E (-270 °C to -200 °C): ±10 °C maximum
±3 ºC maximum
±0.4 ºC maximum for 0 to 60 ºC
±1 ºC maximum
System accuracy at 25 ºC (Using 4 Hz and 17 Hz filters)
±20 µV maximum for ±50 mV inputs
±20 µV maximum for ±100 mV inputs
±3 mV maximum for the pH Sensor (±1.0 V range)
±3 mV maximum for 0-5 V inputs
±3 mV maximum for 1-5 V inputs
±10 mV maximum for 0-10 V inputs
±10 mV maximum for ±10 V inputs
System accuracy at 0 °C to +55 °C (Using 4 Hz and 17 Hz filters)
±40 µV maximum for ±50 mV inputs
±40 µV maximum for ±100 mV inputs
±6 mV maximum for the pH Sensor (±1.0 V range)
±6 mV maximum for 0-5 V inputs
±6 mV maximum for 1-5 V inputs
±20 mV maximum for 0-10 V inputs
±20 mV maximum for ±10 V inputs
User's Manual Pub. 0300266-02 Rev. B
A-3