Section 3.1
Introduction
Section 3.2
About
Communications
Instance:
100
Bit
Analog
data
12 bytes
0×00 -
0×0B
Chapter 3
Configuring the 1734sc-IF4U
Using RSLogix 5000
This chapter covers the following subjects:
•
Introduction
•
About Communications
•
Using Generic Profile
•
Using Add-On Profile (AOP)
•
Module Configuration
•
Reading Input Data
•
Getting Technical Assistance
•
Declaration of Conformity
This chapter will describe how to configure the IF4U module using RSLogix
5000 programming software.
The module produces and consumes data as follows:
IF4U Produce/Consume Data
Description:
Analog Only
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Status Byte for Channel 1
n/a n/a n/a OC OR UR n/a CF n/a n/a n/a OC OR UR n/a CF
Status Byte for Channel 3
n/a n/a n/a OC OR UR n/a CF n/a n/a n/a OC OR UR n/a CF
Total Size:
16 Bytes RSL 5K (Dnet 12 bytes)
Channel 0 Data - INT
Channel 1 Data - INT
Channel 2 Data - INT
Channel 3 Data - INT
Status Byte for Channel 0
Status Byte for Channel 2
User's Manual Pub. 0300266-02 Rev. B