17.1 REMOTE PANEL CONNECTION (VI613 EVO OR V2I810 OR
VTIC10)
It is possible to connect to the instrument up to two remote panels VI613 available with or without temperature
sensor on board, or a V2I810 LCD panel, or a touch panel VTIC10; the use of keyboards VI613 exclude the
possibility of using the keyboard Visograph or Visotouch and vice versa.
Parameters CF55 and CF56 allow to enable the keyboards VI613; the parameter CF74 allows to enable the
V2I810 keyboard or VTIC10.
If the remote terminal VI613 is provided with probe on board, the temperature adjustment can be performed
with the probe of the terminal.
The connection of the remote terminals must be performed using a shielded / twisted cable (such as Belden
8772, wires 1 mm
minimum); the maximum length of VI613 terminal cable is 100 mt. (maximum length of the
2
connection, both if using one or two keyboards), the maximum length of V2I810 or VTIC10 terminal cable is
60mt.
In case of lack of communication between the device and the keyboard (wrong connection, wrong parameters
configuration), the display shows the message "noL" (no link).
When using two keyboards VI613 you must configure the dip switch on the rear of the same, giving the first
keypad address 1 and 2 to the second keypad.