Aa7N - ICP DAS USA I-7021 User Manual

I-7000/7022/7024 series, m-7022/7024/7028 series
Table of Contents

Advertisement

I-7022, M-7022

2.19 $AA7N

Description:
Performs a 10 V calibration on a specified channel.
Syntax:
$AA7N[CHKSUM](CR)
$
Delimiter character
AA
Address of the module to be calibrated (00 to FF)
7
Command for the 10 V calibration
N
Specifies the channel to be calibrated, zero based
Response:
Valid Command:
Invalid Command:
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
Examples:
Command: $0170
Performs a 10 V output calibration on channel 0 of
module 01 and returns a valid response.
Related Commands:
Section 2.8 $AA1N, Section 2.11 $AA3NVV
92
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
!AA[CHKSUM](CR)
?AA[CHKSUM](CR)
Response: !01