Page 1
Modbus RTU and DCON protocols, which can be configured via software. The 7061 series are the ideal solution for high power applications. 2. Terminal Assignment I-7061 12-channel Relay Output DAQ Module - QuickStart (Jul/2018) ICP DAS USA, Inc. | www.icpdas-usa.com...
。 Module Address: 01 。 DIO Type: Type 40 。 Baud Rate: 9600 bps 。 Checksum disabled I-7061 12-channel Relay Output DAQ Module - QuickStart (Jul/2018) ICP DAS USA, Inc. | www.icpdas-usa.com | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717...
Page 3
3. Connect the module to the power supply using the +Vs and GND terminals. Note that the voltage supplied should be in the range of +10 to +30V DC. I-7061 12-channel Relay Output DAQ Module - QuickStart (Jul/2018) ICP DAS USA, Inc. | www.icpdas-usa.com...
Page 4
It can select multi-options such as Baud Rate, Protocol, Checksum, and Format to search module. The default settings for the module can be found in Section 3. Click OK after selecting the COM port setting. I-7061 12-channel Relay Output DAQ Module - QuickStart (Jul/2018) ICP DAS USA, Inc. | www.icpdas-usa.com...
Page 5
DCON Utility Pro supports DCON and Modbus protocol for all ICPDAS and the others modules. 6. Configuration I/O module setting on PC I-7061 12-channel Relay Output DAQ Module - QuickStart (Jul/2018) ICP DAS USA, Inc. | www.icpdas-usa.com | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717...
Page 6
Section 2 for details. Read data from the input channels: send either the #AA or #AAN command to the module. I-7061 12-channel Relay Output DAQ Module - QuickStart (Jul/2018) ICP DAS USA, Inc. | www.icpdas-usa.com | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717...
Page 7
If user doesn’t know command, user can select Address and ID, it will show some refer commands as below. User can select necessary command to test or debug modules. I-7061 12-channel Relay Output DAQ Module - QuickStart (Jul/2018) ICP DAS USA, Inc. | www.icpdas-usa.com...