2.12 $AA4

Description:
Sets the current output as the power-on value.
Syntax:
$AA4[CHKSUM](CR)
$
Delimiter character
AA
Address of the module to be set (00 to FF)
4
Command to set the power on value
Response:
Valid Command:
Invalid Command: ?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
Examples:
Command: #0100.000
Sets the output of module 01 to 0.0mA and returns
a valid response.
Command: $014
Sets the current output of module 01 as the power-
on value and returns a valid response.
78
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
!AA[CHKSUM](CR)
Response: >
Response: !01