ICP DAS USA I-7021 User Manual page 165

I-7000/7022/7024 series, m-7022/7024/7028 series
Table of Contents

Advertisement

Address Description
40492
Host watchdog timeout count, write 0
to clear
40494
Slew rate
00257
Protocol, 0: DCON, 1: Modbus RTU R/W
00260
Modbus host watchdog mode
0: same as I-7000
1: can use AO and DO command to
clear host watchdog timeout status
00261
1: enable, 0: disable host watchdog
00269
Modbus data format, 0: hex, 1:
engineering
00270
Host watch dog timeout status, write 1
to clear host watch dog timeout status
00272
Write 1 to load factory default
calibration parameters. for firmware
version A3.0 and later
00273
Reset status, 1: first read after
powered on, 0: not the first read after
powered on
Output Types
Type Code Output Range
30
31
32
33
34
35
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
Data Format
Engineering
0 ~ 20 mA
Hexadecimal
Engineering
4 ~ 20 mA
Hexadecimal
Engineering
0 ~ 10 V
Hexadecimal
Engineering
-10 ~ 10 V
Hexadecimal
Engineering
0 ~ 5 V
Hexadecimal
Engineering
-5 ~ 5 V
Hexadecimal
Attribute
R/W
R/W
R/W
R/W
R/W
R/W
W
R
Max
Min
20000
0
3FFFh
0000h
20000
4000
3FFFh
0000h
10000
0
3FFFh
0000h
10000
-10000
3FFFh
C000h
5000
0
3FFFh
0000h
5000
-5000
3FFFh
C000h
165